Smoke and flue pipes serving solid-fuel appliances must be cleaned at least once every 3 months, and those serving liquid- and gas-fuel appliances at least once every 6 months. An annual inspection of the chimney flues is also mandatory, and failing to carry it out can result in a fine.
How often flues must be cleaned
According to § 34 section 1 of the Regulation of the Minister of Interior and Administration on fire protection of buildings, other construction objects and areas, deposits must be removed within the following periods of flue use:
- from appliances in collective catering and food service establishments: at least once a month, unless local regulations provide otherwise;
- from other solid-fuel appliances: at least once every 3 months;
- from other liquid- and gas-fuel appliances: at least once every 6 months.
Ventilation flues are cleaned at least once a year, unless operating conditions require more frequent cleaning (§ 34 section 2). The work is carried out by persons holding chimney-sweep qualifications (section 3). This requirement does not apply to single-family houses or farm and holiday buildings (section 4).
Annual chimney inspection
Article 62 section 1 point 1 letter c of the Construction Law requires the owner or manager of a building to have it periodically inspected at least once a year. The inspection covers the technical condition of gas installations and of chimney flues: smoke, exhaust and ventilation flues. The exemption for single-family houses in article 62 section 2 applies only to the inspection under letter a, so their owners must also inspect chimney flues.
Under article 62 section 6, chimney flue inspections are carried out by:
- a master chimney sweep: for smoke flues and gravity-driven exhaust and ventilation flues;
- a person holding construction qualifications in the relevant specialty: for the same flues, as well as industrial chimneys, free-standing chimneys and flues with forced draft from mechanical equipment.
Who is responsible and what the penalties are
Fire protection obligations rest with the building owner (article 4 section 1 of the Act on Fire Protection). A manager or user takes them over under a contract, and where there is none, the person actually in control of the building is liable (section 1a).
Anyone obliged who fails to ensure the removal of deposits from smoke and exhaust flues is liable to arrest, restriction of liberty or a fine (article 82 § 2 point 7 of the Petty Offences Code). The fine amounts to up to PLN 30,000 (article 24 § 1a). Failure to carry out the inspection under article 62 section 1 point 1 is subject to the fine under article 93 point 8 of the Construction Law. The Act does not state its amount, so the range from article 24 § 1 of the Petty Offences Code applies: from PLN 20 to 5,000.
Smoke and carbon monoxide alarms
The Regulation of 21 November 2024 (Journal of Laws item 1716) added § 28a. A residential unit must be equipped with at least one autonomous smoke alarm, unless it is protected by a fire alarm system or a fixed fire extinguishing system. A room in a unit in a ZL zone where solid, liquid or gaseous fuel is burned requires an autonomous carbon monoxide alarm. The exception covers appliances with a sealed combustion chamber and gas cooking appliances.
The regulation entered into force on 23 December 2024. For premises used as residential units on that day, the requirement applies from 1 January 2030 (§ 2 sections 2 and 3), and for rooms providing hotel services from 30 June 2026 (§ 2 section 4). The regulation sets no separate deadlines for other premises.